Interpret status indicators, Ipim module status indicators – Rockwell Automation MDF-SB1304F Kinetix 6000M Integrated Drive-Motor System User Manual
Page 90
![background image](/manuals/580143/90/background.png)
90
Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Chapter 7
Troubleshooting the Kinetix 6000M System
Interpret Status Indicators
When a fault condition is detected, the appropriate status indicator will
illuminate (IDM unit or IPIM module) and the IPIM module will annunciate
the fault on its front panel display. Refer to
for IPIM status indicator
descriptions and
for IDM unit indicators.
IPIM Module Status Indicators
IPIM module fault descriptions, types and actions start on
.
Figure 36 - IPIM Display and Status Indicators
Indicator
Indication
Description
Control
Bus
Status of the
Control Bus
Off
Control bus is not present
Solid Green
Control bus is present
Solid Red
A fault has occurred
Module
Status
IPIM Module
Status
Off
Power is not applied to the module
Flashing Green
Module is in Standby mode - configuration may be required
Solid Green
Module is operating correctly
Flashing Red
A recoverable fault has occurred
(1)
Solid Red
An unrecoverable fault has occurred
Alternating Green/Red
Self-test mode during powerup
Network
Status
Network Status
Off
Not powered or no IP address
Flashing Green
No connections, but an IP address has been obtained
Solid Green
An established connection exists
Flashing Red
A connection has timed out
Solid Red
Duplicate IP is present
Alternating Green/Red
Self-test mode during powerup
DC Bus
Status of the DC
Bus
Off
DC Bus is not present
Flashing Green
DC bus is present and all IDM units are disabled
Solid Green
DC bus is present and at least one IDM unit is enabled
IPIM
01
07
13
02
08
14
03
09
15
04
10
16
05
11
06
12
Info
Tools
Control Bus
Module Status
Network Status
DC Bus
Port 1
Port 2
Control Bus
Module Status
Network Status
DC Bus
Port 1