Rockwell Automation MDF-SB1304F Kinetix 6000M Integrated Drive-Motor System User Manual
Page 84
84
Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Chapter 6
Configuring the Kinetix 6000M System
6. Select the desired Test (Marker/Feedback/Command & Feedback) to
verify connections.
The Online Command dialog box opens. Follow the on-screen test
instructions. When the test completes, the Command Status changes from
Executing to Command Complete.
7. Click OK.
The Online Command - Apply Test dialog box opens (Feedback and
Command & Feedback tests only). When the test completes, the
Command Status changes from Executing to Command Complete.
8. Click OK.
9. Determine if your test completed successfully.
If
Then
Your test completes successfully, this dialog box opens.
1. Click OK.
2. Remove Hardware Enable Input signal
(1)
.
3. Go to Tune the Axes on
(1) The hardware enable input for IDM units is on the IPIM module.
Your test failed, this dialog box opens.
1. Click OK.
2. Verify the Bus status indicator turned
solid green during the test.
3. Verify that the Hardware Enable Input
signal is applied to the axis you are
testing.
4. Verify conversion constant entered in the
Conversion tab.
5. Return to main
and run the test
again.