Upgrading the Kinetix 6000M System Firmware
This appendix provides procedures for upgrading firmware for the
Kinetix 6000M integrated drive-motor (IDM) units and IDM power interface
modules (IPIM).
Upgrading firmware for the Kinetix 6000M system is done by using
ControlFLASH software. The procedure for upgrading the IDM units uses the
sercos interface, similar to axis modules. However, upgrading firmware on the
IPIM module is accomplished over the EtherNet/IP network.
Before You Begin
You need the following software and information before you begin.
Topic
Page
Description
Cat. No.
Firmware Revision or
Software Version
RSLogix 5000
software
9324-RLD300NE
20.01
(2)
or later
(2) Version 20.00 may be used if the motion database has been updated.
ControlLogix sercos module
1756-MxxSE
20.007 or later
CompactLogix sercos module
1768-M04SE
20.007 or later
SoftLogix sercos PCI card
1784-PM16SE
20.007 or later
RSLinx® software
2.59 or later
ControlFLASH software kit
(1)
(1) Download the ControlFLASH kit from
Support at (440) 646-5800 for assistance.
For more ControlFLASH information (not drive specific), refer to the ControlFLASH Firmware Upgrade Kit Quick Start, publication
.
From website
Catalog number of the targeted IPIM module and IDM unit you want to upgrade
Network path to the targeted IPIM module and IDM unit.
IMPORTANT
Control power must be present prior to upgrading your IPIM module or IDM
units.
ATTENTION: To avoid personal injury or damage to equipment during the
firmware upgrade due to unpredictable motor activity, do not apply 3-phase AC
or common-bus DC input power to the IAM module.