beautypg.com

Rockwell Automation 2706 DL20 SERIES G USER MANUAL User Manual

Page 177

background image

Appendix H
Parallel Input Converter

H–5

Panel Mounted Version (Catalog No. 2706–NG2)

1. Secure the converter to the panel.

2. Connect the input converter to the DL20 by wiring terminals 11A through

22 of the 2706–NG2 to the identically numbered terminals on the DL20.

Connecting the AC Inputs

1. Connect up to twelve 120V AC

10%, 60 Hz inputs to the 120V AC

source inputs (D9 through D0, MS1 and MS0) on the parallel input
converter.

2. Connect the AC common to the terminal marked AC COM on the

converter.

Important: The AC voltage on all inputs to the Parallel Input Converter
must be in phase i.e., they must all come from the same power source.