Appendix G
Application Notes

G–19

Figure G.6
DL20 to DC Output Module (Catalog No. 1771-OB, -OG)

00-07

10-17

A

0

1

2

3

4

5

6

7

8

A

0

1

2

3

4

5

6

7

8

+ 12-24 VDC (OB) -

or

+ 5 VDC (OG) -

DL20 Terminals

1771-OB DC Output Modules (12-24 VDC)

or

1771-OG DC Output Modules (5VDC)

D9 D8

D7 D6

D5 D4

D3 D2

D1

MS1 MS0

GND

DO

Set both internal switches in the OG module ON for
high true logic.

+5

VDC
OUT

Important Note: The 1771-OG TTL output modules 5VDC signals are
more noise susceptible than 12-24 DC signals. In applications where noise
may be a problem, it is strongly recommended that a 1771-OB DC output
module be used.

!

ATTENTION: Do not connect to terminal 22 (+5 VDC OUT).
Applying any voltage to this terminal will damage the DL20.