beautypg.com

Rockwell Automation 1753-DNSI DeviceNet Safety Scanner for GuardPLC Controllers User Manual

Page 91

background image

Publication 1753-UM002A-EN-P - July 2005

Monitor Status 10-7

Safety Connection Extended Error Codes

General
Status
Error Code
(00gg)

Extended
Error Code
(nnnn)

Description

0001

0100

The connection is in use.

0001

0103

Transport is not supported.

0001

0106

Ownership conflict occurred.

0001

0107

The connection was not found.

0001

0108

Connection type is invalid.

0001

0109

Connection size is invalid.

0001

0110

The module is not configured.

0001

0111

Expected Packet Rate value is not supported.

0001

0114

This is the wrong module.

0001

0115

Device type is incorrect.

0001

0116

Module revision is incorrect.

0001

0118

The configuration format is invalid.

0001

011A

The application is out of connections.

0001

0203

The connection has timed out.

0001

0204

An unconnected message has timed out.

0001

0205

Unconnected send parameter error occurred.

0001

0206

The message is too large.

0001

0301

There is no buffer memory.

0001

0302

Bandwidth is not available.

0001

0303

Dynamic I/O resources are not sufficient.

0001

0305

Signatures match.

0001

0311

The port is not available.

0001

0312

A link address is not available.

0001

0x0315

Safety Connection Type name is invalid (not equal to 0x50).

0001

0317

The connection is not scheduled.

0001

0x0801

The RPI is not compatible with previously established
multicast connections. All multi-cast consumers must
request the same RPI.

0001

0x0802

Safety connection size is invalid.

0001

0x0803

Safety connection format is invalid.

0001

0x0805

Ping interval EPI multiplier was out of range (10 to 10000).

0001

0x0806

Time Coordination Message Minimum Multiplier was out of
range (10 to 10000).

0001

0x0807

Time Expectation Multiplier was out of range (0 to 42969).

0001

0x080A

CPCRC value in Safety Open and calculated CPCRC value.

0001

0x080B

Time Correction Connection ID is invalid.

0001

0x080C

Configuration Signatures do not match. The Configuration
Signature was non-zero and did not match the value in the
target.