9-2 Verify Your DeviceNet Safety Configuration

appears listing those devices and their current status, including a
device icon overlaid with a status icon.

To return to RSNetWorx for DeviceNet so that you can correct the
status of the indicated devices, close the Safety Device Verification
Wizard by clicking on Cancel.

To skip the devices listed and continue the verification process for
other safety devices on the network, click Next.

Status

Icon

Overlay

Description

Missing

The device is part of the network configuration, but was
not found during the browse operation.

Mismatch

The device identity in the network configuration does
not match the identity of the online device.

Unknown

The device is in the configuration, but has not been
detected on the network yet.

Safety Network
Number Error

The Safety Network Number in the device is either
invalid or does not match the Safety Network Number
for the device in the RSNetWorx for DeviceNet
configuration file.

Signature
Mismatch

none

The configuration signature in the device does not
match the configuration signature in the RSNetWorx for
DeviceNet configuration file.

Safety Locked

The device is already locked.