To successfully transfer data between FactoryTalk Historian ME and the PI server,
you must create two application trusts on the PI server: webs and datatransfer. To do
so, perform the following steps:
1. Launch the OSIsoft SMT application from where you installed it. Navigate to
System Management Tools.
2. After SMT launches, go to the Collectives and Servers pane and click the
checkbox next to the PI server you want to create a trust for.
3. Under the System Management pane, click [+] next to Security and then select
Mappings and Trusts.
4. In the Trusts tab in the main window, select the drop-down menu on the New
option. The Wizard option is checked by default.
The Add Trust Wizard window is launched. The Trust Wizard creates a trust on the PI
server that is currently selected.
5. Select your PI server from the drop-down menu in the FactoryTalk Historian ME
server field.
Trusts
option
Trust menu bar
Wizard option