6. Select your FactoryTalk Historian SE from the drop-down menu in the
FactoryTalk Historian ME server field.
You must create a trust for Data Transfer (datatransfer) and a trust for web
applications (webs). This procedure describes creating a Data Transfer trust first.
Use this procedure to create a web application trust after you create the Data
Transfer trust.
7. Enter a name for the datatransfer trust in the Trust Name field. Click [Next].
The trust description is optional.
8. Select “PI-API application” for the trust type. Click [Next].
9. Enter datatransfer for the application name in the Application Name field.
10. Specify client connection information such as the network path, IP address, and
subnet mask for the datatransfer trust. Click [Next].
11. Select a PI user from the drop-down menu.
12. Click [Finish]. The trust will display in the list of trusts as shown in the following
image.