Communicating with Devices on an Ethernet Network
Generating Custom Data Table Monitor Pages
You can generate Custom Data Table Monitor pages with your text
editor then download them to the SLC 5/05 processor using
RSLogix 500 version 6.0 or later. The first element of the file must
contain a special tag as follows:
xx>
where xx is the automatic refresh rate in seconds (01...99).
A value outside the range defaults to a snapshot display.
You can modify the refresh rate three different ways:
•
Enter the desired refresh rate and press Change
•
Select Default for a 15 second refresh
•
Disable the refresh by selecting Disable
Referencing Data Table Memory - the Data Table locations in the
Custom Data Table Monitor are referenced by placing custom tags into
the ASCII file of the processor. The format of the custom tag is:
[#expand][!comment]>
The items surrounded with {} are sometimes optional, whereas the
items surrounded by [] are always optional.
You must always specify the basic file reference. Depending on which
file is being referenced, file_number or file_element may be defaulted.
If the file_type is I, O or S, the file_number does not need to be
specified, but the file_element must be specified. If the file_type is not
one of the three special files, the file_number must be specified and
the file_element may default to zero (because the input, output and
status files have fixed numbers).