Publication 1747-UM011G-EN-P - June 2008

Specifications 179

1746-P5, 1746-P6, and 1746-P7 Power Supplies

Attribute

Value

1746-P5

1746-P6

1746-P7

Line voltage

90-146V dc

30-60V dc

10-30V dc

(5)

Typical line power requirement

85VA

100VA

12V dc input: 50VA

24V dc input: 75VA

Inrush current, max

20A

20 A (required for turn-on)

Internal current capacity

5 A at 5V dc

0.96 A at 24V dc

12V dc input:

2.0 A at 5V dc 0.46 A at 24V

dc

24V dc input:

3.6 A at 5V dc

0.87 A at 24V dc

See P7 current capacity chart

Fuse protection

(1)

Fuse is soldered in place

24V dc user-power current capacity

200 mA

not applicable

24V dc user-power voltage range

18-30V dc

Ambient temperature, operating

0 °C...60 °C (32 °F...140 °F)

Current capacity is derated 5% above 55 °C (131°F)

Isolation

(2)

1800V ac RMS for 1 s

600V ac RMS for 1 s

CPU hold-up time

(3)

20 ms (full load)

3000 ms (no load)

5 ms (full load)

1500 ms (no load)

12V dc input:

1.37 ms at 0V dc (full load)

895 ms at 0V dc (no load)

10 ms at 9V dc (full load)

continuous at 9V dc (no

load)

24V dc input:

40 ms at 0V dc (full load)

1860 ms at 0V dc (no load)

790 ms at 11V dc (full load)

continuous at 11V dc (no

load)

Certification

(when product is marked)

UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous

Locations
C-UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous

Locations

CE

(4)

European Union 89/336/EEC EMC Directive, compliant with:

EN 50082-2 Industrial Immunity

EN 50081-2 Industrial Emissions

or

EN 61000-6-2 Industrial Immunity

EN 61000-6-4 Industrial Emissions

European Union 73/23/EEC LVD Directive, compliant with safety related portions of:

EN61131-2 Programmable Controllers
C-Tick

Australian Radio Communications Act, compliant with:

AS/NZS 2064 Industrial Emissions

(1)

Power supply fuse is intended to guard against fire hazard due to short-circuit conditions. This fuse may not protect the supply from miswiring or excessive transient in the
power line.

(2)

Isolation is between input terminals and backplane.

(3)

CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.

(4)

See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certification details.

(5)

See page 70 for information on power supply under voltage operation.