beautypg.com

Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 23

background image

Publication 1747-UM011G-EN-P - June 2008

Quick Start for Experienced Users 23

9.

Establish communication to the processor.

Reference

Refer to the following to establish communication between the processor and your
personal computer.

Chapter 8
(Starting Up Your
Control System)

Set the communication parameters of software to match the default parameters of the processor.

Processor

Procedure

SLC 5/01

Connect 1747-PIC interface from the processor to your personal computer serial port or

connect 1747-UIC interface from the processor to your personal computer USB port, or use a

1784-PKTX(D) or 1784-PMCK interface.

SLC 5/02

Connect 1747-PIC interface from the processor to your personal computer serial port or

connect 1747-UIC interface from the processor to your personal computer USB port, or use a

1784-PKTX(D) or 1784-PMCK interface.

SLC 5/03

Connect the 1747-PIC interface from the processor to your personal computer serial port or

connect the 1747-UIC interface from the processor to your personal computer USB port to

the processor by using the 1747-C13 or 1747-CP3 cable. You can also use a 1784-PKTX(D) or

1784-PCMK interface, or a 1747-CP3 cable from channel 0 of the processor to the personal

computer serial port.

SLC 5/04

Connect a 1747-CP3 cable from channel 0 of the processor to the personal computer serial

port or connect the 1747-UIC interface from channel 0 of the processor to your personal

computer USB port, or use a 1784-PKTX(D) or 1784-PCMK interface.

SLC 5/05

Connect a 1747-CP3 cable from channel 0 of the processor to the personal computer serial

port, or connect the 1747-UIC interface converter from channel 0 of the processor to your

personal computer USB port. For Ethernet connection, connect channel 1 of the processor
and the PC Ethernet card to an Ethernet hub by using 10/100Base-T compatible cable.

(1)

(1)

EtherNet/IP address must first be set via BOOTP or an RS-232 connection. See appendix C for more information.

Comms Channel

Channel 0
Configuration

Channel 1 Configuration

SLC 5/01 and 5/02

SLC 5/03, 5/04, and 5/05 SLC 5/03

SLC 5/04

SLC 5/05

DH-485:

19.2 Kbaud

node address = 1

DF1 Full-duplex:

no handshaking

19.2 Kbaud

CRC Error Check

duplicate packet,

detect on

no parity

DH-485:

19.2 Kbaud

node address = 1

DH+:

57.6 Kbaud

node address = 1

Ethernet:

BOOTP enabled