Troubleshooting 151

FLT status indicator is

on

All other status

indicators are off

Status of any

Communication status

indicator does not

matter

Inadequate system

power

Improper line

power voltage

selection.

Verify proper 120/240V power supply jumper selection. See

page 106.

Power status indicator

is on

All other status

indicators are off

Status of any

Communication status

indicator does not

matter

Processor not in

run mode

Either improper

mode selected or

user program logic

error.

1. Verify selected processor mode.

2. If in program or test mode, try to enter run mode.

a. If the keyswitch is in the REM position and there is no key,

use the programmer.

b. If the keyswitch is in the REM or PROG position and you

have the key, toggle to the RUN position.

3. If in suspend mode, check user program logic for suspend

instructions.

Line power out of

operating range.

1. Check proper 120/240V power supply jumper selection and

incoming power connections.

2. Monitor for proper line voltage at the incoming power

connections.

Improper seating of

power supply

and/or processor in

the chassis.

1. Remove power and inspect the power supply and processor

chassis connections.

2. Re-install the devices and re-apply power.

IMPORTANT

The processor only operates in slot 0 of the first chassis.

Defective

processor, power

supply, or chassis.

1. Attempt to put processor in run mode in existing chassis.

a. If the keyswitch is in the REM position and there is no key,

use the programmer.

b. If the keyswitch is in the REM or PROG position and you

have the key, toggle to the RUN position.

2. Place the processor in another chassis. Apply power,

reconfigure, and attempt to put processor in run mode. If

unsuccessful, replace the processor.

3. Place the power supply in another chassis and test. If

unsuccessful, replace the power supply. If successful,

replace the original chassis.

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action