Troubleshooting

Power status indicator

is on

Run status indicator is

on

Force status indicator is

on

All other status

indicators are off

Status of any

Communication status

indicator does not

matter

System does not

operate per ladder

logic

User forced I/O is

disabling operation.

1. Monitor program file on-line and identify forced I/O.

2. Disable appropriate forces and test system conditions again.

Power status indicator

is on

Run status indicator is

on

Force status indicator is

flashing

All other status

indicators are off

Status of any

Communication status

indicator does not

matter

System does not

operate per

programmed

forces

User programmed

forces are not

enabled.

1. Monitor program file on-line and identify programmed

forces.

2. Enable appropriate forces and test system conditions again.

Once forces are enabled, the Force status indicator turns on

(steady).

Power status indicator

is on

FLT status indicator is

flashing

Batt status indicator is

on

All Other status

indicators are off

Status of any

Communication status

indicator does not

matter

CPU major error

with low or no

battery back-up

Loss of RAM during

power-down.

1. Verify battery is connected. See page 137.

2. Replace the battery if you want RAM battery backup. See

page 137.

3. Refer to processor major fault recommended action steps.

SLC 5/03, SLC 5/04, and SLC 5/05 Processor Errors

If the status indicators
indicate

The following
error exists

Probable Cause

Recommended Action