beautypg.com

Features of an i/o module, Wiring your i/o module, Features of an i/o module wiring your i/o module – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual

Page 116: Below is an example of a combination i/o module

background image

Publication 1747-UM011G-EN-P - June 2008

116

Wiring Your I/O Modules

Features of an I/O Module

Below is an example of a combination I/O module.

Wiring Your I/O Module

Terminals on the modules have self-lifting pressure plates that accept
two 2 mm

2

(14 AWG) wires. Series B 12-point and 16-point and

analog modules are equipped with removable terminal blocks for
ease of wiring. The plug for the removable terminals is also color
coded:

red (ac)

blue (dc)

orange (relay)

green (specialty).

Status indicators on the front of each module display the status of
each I/O point. The status indicators illuminate when the proper
signal to an input terminal is applied or when the processor
commands an output to be energized.

To locate the I/O module wiring diagrams, contact your Rockwell
Automation sales office for the latest selection guide, publication
1747-SG001. Or, locate the installation instruction sheet that was sent
with your I/O module. It also includes I/O wiring diagrams.

1

2

3

4

5

0

1

2

3

4

5

0

OUTPUT

INPUT

I/O Status
Indicators

Terminal Block Screw
(maximum torque: 0.6 Nm (5.3 lb-in))

Hinged Wiring Terminal
Door with Label

Color Band

Input and Output Terminals
Connected to Terminal Block

Terminal Block (may be color-coded
and removable on some modules)

Terminal Wiring

2 wires per terminal maximum

#14 AWG (2mm

2

) maximum

Maximum torque: 0.9 Nm (8 lb-in)

Tie Wire

Wires Leading to Input and Output Devices

Terminal Block Screw
(maximum torque: 0.6 Nm (5.3 lb-in))