Features of an i/o module, Wiring your i/o module, Features of an i/o module wiring your i/o module – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual
Page 116: Below is an example of a combination i/o module
Publication 1747-UM011G-EN-P - June 2008
116
Wiring Your I/O Modules
Features of an I/O Module
Below is an example of a combination I/O module.
Wiring Your I/O Module
Terminals on the modules have self-lifting pressure plates that accept
two 2 mm
2
(14 AWG) wires. Series B 12-point and 16-point and
analog modules are equipped with removable terminal blocks for
ease of wiring. The plug for the removable terminals is also color
coded:
•
red (ac)
•
blue (dc)
•
orange (relay)
•
green (specialty).
Status indicators on the front of each module display the status of
each I/O point. The status indicators illuminate when the proper
signal to an input terminal is applied or when the processor
commands an output to be energized.
To locate the I/O module wiring diagrams, contact your Rockwell
Automation sales office for the latest selection guide, publication
1747-SG001. Or, locate the installation instruction sheet that was sent
with your I/O module. It also includes I/O wiring diagrams.
1
2
3
4
5
0
1
2
3
4
5
0
OUTPUT
INPUT
I/O Status
Indicators
Terminal Block Screw
(maximum torque: 0.6 Nm (5.3 lb-in))
Hinged Wiring Terminal
Door with Label
Color Band
Input and Output Terminals
Connected to Terminal Block
Terminal Block (may be color-coded
and removable on some modules)
Terminal Wiring
•
2 wires per terminal maximum
•
#14 AWG (2mm
2
) maximum
•
Maximum torque: 0.9 Nm (8 lb-in)
Tie Wire
Wires Leading to Input and Output Devices
Terminal Block Screw
(maximum torque: 0.6 Nm (5.3 lb-in))