The 1761-net-dni devicenet interface – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual
Page 234
Publication 1747-UM011G-EN-P - June 2008
234
Control Networks
DeviceNet Network
The 1761-NET-DNI DeviceNet Interface
The DeviceNet Interface (DNI) is an intelligent DeviceNet-to-DF1 protocol
conversion device that let existing DF1 devices communicate on DeviceNet
network. The DF1 device is able to exchange I/O data with a master device
and is able to initiate and receive DF1 encapsulated DeviceNet messages
across a DeviceNet network.
The DNI provides a single DeviceNet connection point and a single RS-232
connection. The DeviceNet port is isolated from the DNI digital logic and
RS-232 port.
The primary functions of the DNI are:
•
to collect and receive input data from the DF1 device connected on its
RS-232 port and forward that data to a connected master on a
DeviceNet network.
•
to monitor output data received from the DeviceNet master and write
that data to the DF1 device.
•
to let DF1 devices send and receive messages across the DeviceNet
network.
The DNI can be used to interconnect:
•
MicroLogix controllers.
•
PLC-5 programmable controllers.
•
operator interface devices.
•
SLC 5/03, SLC 5/04, and SLC 5/05 processors.
SLC 5/02 or later
processor
1747-SDN Scanner
1770-KFD Interface
Personal
Computer with
RSNetworx for
DeviceNet
Software
RS-232
cable
DeviceNet
Devices
RediSTATION
Panel
1305 Drive
Flex I/O Controller
DeviceNet Network