Power supply specifications – Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual
Page 177

Publication 1747-UM011G-EN-P - June 2008
Specifications 177
Power Supply
Specifications
This section provides specifications for the SLC 500 power supplies.
1746-P1, 1746-P2, 1746-P3, and 1746-P4 Power Supplies
Certification (when
product is marked)
UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous Locations
C-UL Listed Industrial Control Equipment for Class I, Division 2, Groups A, B, C, D Hazardous Locations
CE
(3)
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2 Industrial Immunity
EN 50081-2 Industrial Emissions
or
EN 61000-6-2 Industrial Immunity
EN 61000-6-4 Industrial Emissions
European Union 73/23/EEC LVD Directive, compliant with safety related portions of:
EN61131-2 Programmable Controllers
C-Tick, Australian Radio Communications Act, compliant with:
AS/NZS 2064 Industrial Emissions
(1)
RTC should not be relied upon for time-based periodic control. Use STI subroutine for periodic control.
(2)
See Capacitor Memory Backup vs. Temperature Curve.
(3)
See the Product Certification link at
.com for Declarations of Conformity, Certificates, and other certification details.
(4)
SLC 5/04 processors manufactured prior to April 2002 draw 200 mA at 24V dc. Check your label to verify your processor’s current draw.
Attribute (1747-)
SLC 5/01
SLC 5/02
SLC 5/03
SLC 5/04
SLC 5/05
L511
L514
L524
L531
L532
L533
L541
L542
L543
L551
L552
L553
Attribute
Value
1746-P1
1746-P2
1746-P3
1746-P4
Line voltage
85...132/170...265V ac, 47...63 Hz
19.2....28.8V dc
85...132/170...265V ac 47...63
Hz
Typical line power requirement
135VA
180VA
90VA
240VA
Inrush current, max
20 A
45 A
Internal current capacity
2 A at 5V dc
0.46 A at 24V dc
5 A at 5V dc
0.96 A at 24V dc
3.6 A at 5V dc
0.87 A at 24V dc
10.0 A at 5V dc
2.88 A at 24V dc
(10)
Fuse protection
(1)
1746-F1 or
equivalent
(5)
(6)
1746-F2 or
equivalent
(5)
(8)
1746-F3 or
equivalent
(5)
(9)
Fuse is soldered in place
24V dc user-power current capacity
200 mA
not applicable
1 A
(1)
24V dc user-power voltage range
18...30V dc
20.4...27.6V dc
User-supplied overcurrent protection, max
(2)
15 A
not applicable
15 A
Ambient temperature, operating
0 °C...60 °C (32 °F...140 °F)
Current capacity is derated 5% above 55 °C (131°F)
0 °C...60 °C (32 °F...140 °F) no
derating
Isolation
(3)
1800V ac RMS for 1 s
600v ac rms for
1 s
2600V dc for 1 s