Rockwell Automation 1747-L5xx SLC 500 Modular Hardware Style User Manual User Manual
Page 195
Publication 1747-UM011G-EN-P - June 2008
Setting Up the DH-485 Network 195
Single Cable Connection
Multiple Cable Connection
Wire/Terminal Connections for DH-485 Connectors for Belden #3106A
Wire/Terminal connections for DH-485 connectors for Belden #9842.
For this wire/pair
Connect this wire
To this terminal
Shield/drain
Non-jacketed
Terminal 2 - Shield
Blue
Blue
Terminal 3 - (Common)
White/drain
White with orange stripe
Terminal 4 - (Data B)
Orange with white stripe
Terminal 5 - (Data A)
For this wire/pair
Connect this wire
To this terminal
Shield/drain
Non-jacketed
Terminal 2 - Shield
Blue/white
White with blue stripe
Cut back - no connection
(1)
(1)
To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the insulation jacket is removed. This wire is not used by DH-485.
Blue with white stripe
Terminal 3 - (Common)
White/orange
White with orange stripe
Terminal 4 - (Data B)
Orange with white stripe
Terminal 5 - (Data A)
IMPORTANT
In 1747-AIC interface series A, terminal 5 was called DATA B
and terminal 4 was called DATA A. In this case, use terminal
numbers only and ignore signal names DATA B and DATA A. The
internal circuitry of the series A is the same as series B.
6 Termination
5 A
4 B
3 Common
2 Shield
1 Chassis
Ground
Orange with White Stripes
White with Orange Stripes
Shrink Tubing
Recommended
Blue (#3106A) or Blue with
White Stripes (#9842)
Drain Wire
Belden #3106A or #9842
to Previous Device
to Successive Device