Connecting CompactLogix Controllers on Ethernet 8-7

Figure 8.5 ENI #1 Configuration - Message Routing Screen

Before we download our configuration to ENI #1, we must configure
the “Utility Settings” tab in the ENI/ENIW Configuration Utility.
Choose the following settings.

Figure 8.6 ENI #1 Configuration - Utility Settings Screen

Then, connect the serial cable between your computer and ENI #1
and click on the ENI IP Addr tab. From this tab, under the “Save To”
column, click the ENI ROM button. This downloads your
configuration parameters to ENI #1 and saves it to non-volatile
memory.

Configure ENI #2

ENI #2 is connected to the CompactLogix controller. This ENI/ENIW
must be configured with its own IP address (131.200.50.94 for this
example) and we must add the IP addresses of the SLC 5/05 controller
and the 1756-ENBT/ControlLogix controller to its Message Routing
table. The Message Routing table allows for up to 50 IP addresses to