A - specifications, Physical specifications, Series c and d ethernet specifications – Rockwell Automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) User Manual User Manual
Page 127: Micrologix web site, Appendix a, Specifications, Appendix
1
Publication 1761-UM006E-EN-P - August 2005
Appendix
A
Specifications
Physical Specifications
Series C and D Ethernet
Specifications
Communication Rate: Auto-negotiates 10 Mbps, full- or half-duplex
and 100 Mbps, full- or half-duplex
Connector: 10/100-Base-T
MicroLogix Web Site
Visit http://www.ab.com/micrologix for more information on
MicroLogix products. You can find a variety of application information
and White Papers covering specific technical topics.
Description
ENI/ENIW Specification
24V dc Power Source Requirement
20.4 to 26.4V dc
24V dc Current Draw
50 mA typical, 100 mA maximum
Maximum Inrush Current
200 mA
Internal Isolation
710V dc for one minute
Vibration
operating: 10 to 500 Hz, 5.0g, 0.030 in. peak-to-peak, 2 hour each axis
Shock
operating: 30g, ±3 times each axis
non-operating: 35g (DIN Rail Mount) 50g (Panel Mount), ±3 times each axis
Operating Ambient Temperature
0
° C to +60° C (+32° F to +140° F)
Storage Temperature
-40
° C to +85° C (-40° F to +185° F)
Humidity
5% to 95% relative humidity (non-condensing)
Agency Certification
(1)
• UL 1604
• C-UL C22.2 No. 213
• Class I Division 2 Groups A,B,C,D
• CE compliant for all applicable directives
• C-Tick marked for all applicable acts
Radiated and Conducted Emissions:
EN 50081-2, Class A
The module has passed testing at the following levels:
• ESD Immunity (EN 61000-4-2)
• 4 kV contact, 8 kV air, 4 kV indirect
• Radiated Immunity (EN 61000-4-3)
• 10V/m, 80 to 1000 MHz, 80% amplitude modulation, and 900 MHz keyed carrier
• Fast Transient Burst (EN 61000-4-4)
• Power supply: 2 kV, 5 kHz
• RS-232 and Ethernet: 1kV, 5 kHz
• Surge Immunity (EN 61000-4-5)
• Power Supply: 500V
• Ethernet (unshielded cable): 2 kV
• RS-232 and Ethernet (shielded cable): 1 kV galvanic gun
• Conducted Immunity (EN 61000-4-6)
• Power Supply: 10V, 0.15 to 80 MHz
• RS-232 and Ethernet (unshielded cable): 3V, 0.15 to 80 MHz
• RS-232 and Ethernet (shielded cable): 10V, 0.15 to 80 MHz
(1) Shielded Ethernet cable required for marine certification.