beautypg.com

Node 254 - ethernet hardware address -13, Node 254 - ethernet hardware address, 248 save/reset – Rockwell Automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) User Manual User Manual

Page 53

background image

Publication 1761-UM006E-EN-P - August 2005

ENI/ENIW Configuration (Nodes 241 to 254) 4-13

These parameters are described in more detail in the following
sections.

Node 254 - Ethernet Hardware Address

You will find the hardware address on a label affixed to the ENI/ENIW
as shown to the left. The hardware address can also be read from
node address 254.

250

TCP/IP Configuration

Integers

4, 8, 12, 16,
or 20

Valid IP Address

000.000.000.000
192.168.1.254

(5)

249

From String

ASCII String

1

ENI/ENIW Identifier

[email protected]

(3)

248

Save/Reset

(4)

Integer

1

0 = save configuration to flash
1 = simple reset
2 = reset to out-of-box
defaults
3 = reset to out-of-box, except
maintain current IP
configuration

n/a

245

Configuration Security
Mask

(5)

Integers

4

Valid IP Address

000.000.000.000

244

SMTP Authentication

(5)

Integer

1

0 = Disabled
1 = Enabled

Disabled

243

SMTP Password

(5)

ASCII String

1

64 character password

null

242

SMTP Username

(5)

ASCII String

1

64 character username

null

241

Ethernet Speed/Duplex

(5)

Integer

1

0 = Auto Negotiate
1 = 10 Mbps half-duplex
2 = 10 Mbps full-duplex
3 = 100 Mbps half-duplex
4 = 100 Mbps full-duplex

10 Mbps half-duplex (series A, B)
Auto Negotiate (series C, D)

(1) Changes to the Baud Rate take effect when the ENI/ENIW power is cycled, or the configuration is saved to flash.
(2) Series C and higher.
(3) The ENI/ENIW address, 192.168.1.254 will be replaced by the IP address assigned to the ENI/ENIW. For example, the string may be [email protected]. If

the ENI/ENIW does not have an assigned IP address, the string will be read as [email protected] for the series D or [email protected] for series A, B,
or C.

(4) See page 4-19 for more information on Save/Reset.
(5) Series D only.

Table 4.1 Configuration Node Functions

Node

Function

Data Type

Number of
Elements

Options

Default

CAT

FRN

1761-NET-ENI

2.20

SER

B

EXTERNAL POWER REQUIREMENTS

24 V dc +10/-15% AT 100 mA

N.E.C. CLASS 2

USE EXTERNAL DC SOURCE
FOR CLASS

I

DIVISION 2

APPLICATIONS. SEE
INSTALLATION INSTRUCTIONS

24VDC

CHS

GND

NEUT

DC

MADE IN U.S.A.

ETHERNET ADDRESS

C

US

R

LISTED IND.CONT.EQ. FOR HAZ.
LOC. A196
OPERATING TEMPERATURE CODE T3C

ETHERNET
INTERFACE

CLASS I, GROUPS A,B,C, AND D, DIV 2

N223

E N I * B 2 2 0 0 1 0 2 0 0 0 1

F A C .

x x

F F -F F -F F -F F -F F -F F

Hardware
Address

This manual is related to the following products: