ENI/ENIW Configuration (Nodes 241 to 254) 4-21
The ENI/ENIW performs the following Email Authentication
configuration operations when receiving a 485CIF/PLC2 Unprotected
Write message of one element (integer) to Node 244.
• 0 = Disabled
• 1 = Enabled
Node 243 - SMTP Email Authentication Password (Series D Only)
Many open mail servers now require user authentication for email.
Node 243 allows a 45 character Password to be defined for email
service (series D units only). Criteria for the Password includes:
• SMTP Email Authentication must be enabled. See Node 244 on
page 4-20.
• The Password remains at the default value unless changed by
the user. See page 4-12 for the Password default values.
• The Password cannot contain any spaces or special ASCII
characters.
• The maximum length of the Password is 45 characters. Any
additional characters are ignored.
• To configure the Password, initiate a message with a string
element as the data. See the message instruction procedure on
page 4-25.
Node 242 - SMTP Email Authentication Username (Series D Only)
Many open mail servers now require user authentication for email.
Node 242 allows a 45 character username to be defined for email
service (series D units only). Criteria for Username includes:
• SMTP Email Authentication must be enabled. See Node 244 on
page 4-20.
• The Username remains at the default value unless changed by
the user. See page 4-12 for the Username default.
• The Username cannot contain any spaces or special ASCII
characters.
• The maximum length of the Username is 45 characters. Any
additional characters are ignored.
• To configure the Username, initiate a message with a string
element as the data. See the message instruction procedure on
page 4-25.