Default settings -5, Default settings – Rockwell Automation 1761-NET-ENIW MicroLogix Ethernet Interface (ENI) User Manual User Manual
Page 17
![background image](/manuals/579286/17/background.png)
Publication 1761-UM006E-EN-P - August 2005
Product Overview 1-5
Default Settings
The ENI/ENIW has the following default settings:
IMPORTANT
The IP addresses in any of the examples in this
manual were arbitrarily assigned and should only be
used on an isolated Ethernet network. Contact your
system administrator for unique IP addresses if you
are connecting your Ethernet devices to your
employer’s Ethernet network.
Table 1.4 RS-232 Settings
Setting
Default
Other Options
Baud Rate
Autobaud
see table 4.2
Handshaking (hardware, software)
none
none
Data Bits
8
none
Stop Bits
1
none
Parity
none
none
Table 1.5 DF1 Settings
Setting
Default
Other Options
Duplicate Message Detection
Enabled
none
Error Detection
Auto-detect (for
Autobaud)
Auto-detect when
Autobaud is true,
otherwise CRC
Embedded Response Operation
Disabled
(1)
(1) Connected controllers should be configured for Embedded Responses Disabled or Auto-detect.
none
DLE ACK Timeout
1 second
none
DLE NAK Receive
3 NAK retries
none
DLE ENQ for Response
3 ENQs retries
none
DF1 Node Address
Don’t Care