9-2 Troubleshooting
LED Sequence at Power-Up
The following LED test is performed at power-up.
Table 9.1 Series A/B LED Sequence at Power-Up (No Ethernet Connection)
LED
Power-Up Sequence
Ethernet TX/RX, Link and FAULT
1. on solid for 2 seconds
FAULT
2. flashes for 3 seconds
Ethernet TX/RX and FAULT
3. on solid for 1/4 second
RS-232 TX/RX
4. flashes if Baud Rate is configured for Auto
(default)
FAULT
5. off, unless an error condition exists
(see troubleshooting table on page 9-3)
Table 9.2 Series C LED Sequence at Power-Up (No Ethernet Connection)
LED
Power-Up Sequence
FAULT
1. flashes for 4 seconds
RS-232 TX/RX
2. flashes if Baud Rate is configured for Auto
(default)
FAULT
3. off, unless an error condition exists
(see troubleshooting table on page 9-4)
Table 9.3 Series D LED Sequence at Power-Up (No Ethernet Connection)
LED
Power-Up Sequence
Ethernet Link
1. flashes green once
Ethernet TX/RX
2. flashes amber, then solid green for 1 second
FAULT
3. flashes for 2 seconds
Ethernet TX/RX
4. flashes amber once
RS-232 TX/RX
5. flashes if Baud Rate is configured for Auto
(default)
FAULT
6. off, unless an error condition exists
(see troubleshooting table on page 9-5)