Troubleshooting 9-5
Table 9.6 Series D LED Indicators
LED
Description
Color
State
Indicates
POWER
module power
green
on
The module is powered.
off
The module does not have power.
RS-232
TX/RX
RS-232 data
transmission
indicator
green
flashing
Data is being transmitted or received over the RS-232 port.
off
No RS-232 traffic.
LINK
Ethernet
activity status
and 10-Base-T
or 100-Base-T
indicator
off
No link or continuous data activity on 10MB Ethernet.
amber
on
10-Base-T link is good.
green
on
100-Base-T link is good.
TX/RX
Ethernet
activity status
and half-duplex
or full-duplex
indicator
Off
No activity.
amber
flashing
Half-duplex data activity.
(1)
green
flashing
Full-duplex data activity.
(1)
FAULT
fault condition
indicator
red
on
lit when a fault condition is present, possible causes
• Duplicated IP address on network
• Network controller error
flashing
one of the following:
• faulty network connection at power up
• ENI/ENIW does not have a saved IP address (uses default IP address
192.168.1.254)
• No BootP/DHCP response
off
Hardware is functioning normally.
(1) Any Ethernet network activity; not necessarily to/from the ENI/ENIW.