Troubleshooting

Publication 1395.5.37 – March, 1999

Message:

CN-16-CLASS 3 TIMEOUT

Fault Type: Soft/Warning/None
Cause:

Drive timed out on scheduled control data reception
from a device.

Action:

Check connections & cables. Check that all devices that
are configured on the network to have a class 3
connection to the drive operational. Check programming
within the PLC or any other device with a class 3
connection to the drive. Check for general errors
occurrring on the network. Check that the network was
not being re-configured.

Message:

CN-17-PLUG FAILURE

Fault Type: Hard
Cause:

Internal Fault detected

Action:

Check version of Adapter Board for compatibility with
Main board. If condition persists, replace adapter board.

Message:

CN-30-ADAPTER PROCESSOR FAULT
CN-31-ADAPTER PROCESSOR FAULT
CN-32-ADAPTER PROCESSOR FAULT

Fault Type: Warning
Cause:

Adapter internal diagnostic malfunction.

Action:

Check version of Adapter Board for compatibility with
Main board.

Message:

CN-44-ADAPTER PROCESSOR FAULT

Fault Type: Hard
Cause:

Adapter internal diagnostic malfunction.

Action:

Check version of Adapter Board for compatibility with
Main Board. If condition persists, replace adapter board.

Message:

CN-45-ADAPTER PROCESSOR FAULT

Fault Type: Hard
Cause:

Adapter internal diagnostic malfunction.

Action:

Check version of Adapter Board for compatibility with
Main board. If condition persists, replace adapter board.

Message:

CN-50-ILLEGAL MAC ID

Fault Type: Hard
Cause:

Node address is <2 or >99

Action:

Check dip switch settings and reset Drive, if condition
persists replace adapter board.

Status LED Indications

Refer to Tables 2.A and 2.B for LED indications.