Write Parameter Data

This function writes a parameter value to the Drive.

PLC Block Transfer Instruction Data –

Write

Read

Size In Elements:

6

6

Processor Type:

PLC–5

PLC–5

Destination Address:

N40:0–5

N40:0–5

Message Structure –

0

PLC Message Write

PLC Message Read

NOTE:

Word 4 of the PLC Message Read instruction is broken down
into two bytes. The High byte contains the status bits

The Low byte contains the Drive message length in bytes.

Header
Word 1

0

Function Code
515

Message Length
See Examples

Header
Word 2

Header
Word 3

Header
Word 4

Data
Word 5

Parameter #

0

Header
Word 1

0

Function Code
515

See Note

Header
Word 2

Header
Word 3

Header
Word 4

Parameter
Status

Data
Word 5

Parameter #

Data
Word 6

Parameter
Data

Data
Word 6

Message Operation – The WRITE PARAMETER DATA function
requests the Drive to change the value of a parameter specified in the
message to the value contained in the message. The value must be sent
to the Drive in Drive units and may need to be scaled by the PLC
Controller prior to being sent.