beautypg.com

Cna board fault messages – Rockwell Automation 1395 ControlNet Communication Board User Manual

Page 69

background image

6–5

Troubleshooting

Publication 1395.5.37 – March, 1999

CNA Board Fault Messages

The fault messages produced by the CNA board are:

Message:

CN-10-PLC OUT OF RUN MODE

Fault Type: Hard
Cause:

PLC was switched from run mode to another mode.

Action:

Check PLC mode switch and I/O control reset, if
condition persists, replace adapter board.

Message:

CN-12-CONTROL NET COMM LOSS

Fault Type: Soft/Warning/None
Cause:

Communication Link Broken

Action:

Check connections & cable. Check that PLC is
operational.

Message:

CN-13-CLASS 1 CLOSE

Fault Type: Soft/Warning/None
Cause:

Scanner Device (PLC) closed the connection to the drive.
This could be due to a timeout condition or due to action
initiated by the Scanner due to programming or possible
error recovery.

Action:

Check connections & cable. Check state of the Scanner
Device (PLC). Check programming within the PLC.

Message:

CN-14-CLASS 3 CLOSE

Fault Type: Soft/Warning/None
Cause:

Device closed a messaging connection to the drive. This
could be due to a timeout condition or due to action
initiated by the device due to programming or possible
error recovery.

Action:

Check connections & cable. Check the state of all devices
that are configured on the network to have a class 3
connection to the drive. Check programming within the
PLC or any other device with a class 3 connection to the
drive.

Message:

CN-15-CLASS 1 TIMEOUT

Fault Type: Soft/Warning/None
Cause:

Drive timed out on scheduled control data reception
from the Scanner Device (PLC).

Action:

Check connections & cables. Check that PLC is
operational. Check for general errors occurring on the
network. Check that the network was not being
re-configured.