Configuration & PLC Interfacing

Publication 1395–5.37– March, 1999

Upload Configuration Link

This function uploads the configuration table information from the Drive
in blocks. Each block of configuration data has a separate function code.

PLC Block Transfer Instruction Data –

Write Read

Size In Elements:

4

4

Processor Type:

PLC-5

PLC-5

Destination Address:

N15:0-3

N15:0-23

Message Structure –

0

PLC Message Write

PLC Message Read

NOTE:

Word 4 of the PLC Message Read instruction is broken down
into two bytes. The High byte contains the status bits

The Low byte contains the Drive message length in bytes.

The “x” designator is a position holder. It could represent
parameter 150, 250, 350, etc. depending on which configura
tion table is being requested.

Header
Word 1

0

Function Code
see table

Header
Word 2

Header
Word 3

0

Header
Word 1

0

See Table

48

Header
Word 2

Header
Word 3

Header
Word 4

Header
Word 4

8

Parameter # (X50)

Header
Word 5

Parameter # (X51)

Header
Word 5

Parameter # (X52)

.

Header
Word 6

.

Parameter # (X69)

Header
Word 23

Upload Function Codes

Function Code

Parameter Numbers

#50 – #69

#150 – #169

#250 – #269

#350 – #369

#450 – #469

260

516

772

1028

1284

Message Operation – The UPLOAD CONFIGURATION LINKS
function requests a listing of the Drive configuration links from the Drive
for use in the PLC Controller. This command is broken down into five
groups of tables.