Read trend information – Rockwell Automation 1395 ControlNet Communication Board User Manual

Page 49

background image

3–35

Configuration & PLC Interfacing

Publication 1395–5.37– March, 1999

Read Trend Information

This function reads the Trend information from the Drive. The Trend
information is broken down into three separate blocks of data. Each
block uses the same function code with the message specifing which
block is to be read.

PLC Block Transfer Instruction Data –

Write

Read

Size In Elements:

4

10

Processor Type:

PLC-5

PLC-5

Destination Address:

N40:0-3

N40:0-9

Message Structure –

Message Header Information:
Word 1
: 0
Word 2: 0
Function Code, Word 3: 1549
Write Message Length, Word 4: 8 bytes

0

PLC Message Write

PLC Message Read

NOTE:

Word 4 of the PLC Message Read instruction is broken down
into two bytes. The High byte contains the status bits

The Low byte contains the Drive message length in bytes.

Header
Word 1

0

Function Code
1549

Message Length
8 bytes

Header
Word 2

Header
Word 3

Header
Word 4

0

Header
Word 1

0

Function Code
1549

See Note

Header
Word 2

Header
Word 3

Header
Word 4

Data
Word 5

Data
Word 6

Parameter
#

Parameter
Data

Parameter
#

Parameter
Data

Data
Word 7

Data
Word 8

Parameter
#

Parameter
Data

Data
Word 9

Data
Word 10

Trend Number – This is an integer number used to specify which
trend buffer the Drive will provide data for.

Trend Buffer #1 – 1
Trend Buffer #2 – 2
Trend Buffer #3 – 3
Trend Buffer #4 – 4