Autotune Update Motor Inertia

This function updates the Drives internal database with the motor
inertia (parameter 613) calculated by the autotune firmware and
provides the data to the PLC Controller.

PLC Block Transfer Instruction Data –

Write

Read

Size In Elements:

4

6

Processor Type:

PLC-5

PLC-5

Destination Address:

N40:0-3

N40:0-5

Message Structure –

0

PLC Message Write

PLC Message Read

NOTE:

Word 4 of the PLC Message Read instruction is broken down
into two bytes. The High byte contains the status bits

The Low byte contains the Drive message length in bytes.

Header
Word 1

0

Function Code
525

Message Length
8 bytes

Header
Word 2

Header
Word 3

Header
Word 4

0

Header
Word 1

0

Function Code
525

See Note

Header
Word 2

Header
Word 3

Header
Word 4

Data
Word 5

Data
Word 6

Parameter
613

Parameter
Data

Message Operation – The AUTOTUNE UPDATE MOTOR
VELOCITY function updates the Drives internal database with the
motor inertia (parameter 613) calculated by the autotune firmware and