Page 47

background image

3–33

Configuration & PLC Interfacing

Publication 1395–5.37– March, 1999

Autotune Tune Velocity Loop

This function calculates the required velocity loop gains based on the
data determined by the motor inertia test, system inertia test, and
damping factor (Parameter #702).

PLC Block Transfer Instruction Data –

Write

Read

Size In Elements:

4

6

Processor Type:

PLC-5

PLC1-5

Destination Address:

N40:-3

N40:0-7

Message Structure –

0

PLC Message Write

PLC Message Read

NOTE:

Word 4 of the PLC Message Read instruction is broken down
into two bytes. The High byte contains the status bits

The Low byte contains the Drive message length in bytes.

Header
Word 1

0

Function Code
1037

Message Length
8 bytes

Header
Word 2

Header
Word 3

Header
Word 4

0

Header
Word 1

0

Function Code
1037

See Note

Header
Word 2

Header
Word 3

Header
Word 4

Data
Word 5

Data
Word 6

Parameter
702

Parameter
Data

Message Operation – The AUTOTUNE TUNE VELOCITY LOOP
function calculates the Drives velocity loop parameters using the data
determined by the motor inertia test, system inertia test, and the
damping factor (Parameter #702).