Configuration & PLC Interfacing

Publication 1395–5.37– March, 1999

The PMW length is determined by adding the message header length
(4 words) to the number of words required to specify the parameter list
and data. Parameter and data change requires two words in the PMW
instruction. Below is an example:

Example 1:
The PLC Controller is to read 1 parameter value from the Drive.

Message Header

PMW

PMR

Word 3

Message Header

4

4

8 bytes

Parameter Data

1

2

2 bytes

Total

5 words

6 words

10 bytes

The PMR message is structured the same as the PMW instruction with
the exception that the Drive will provide a status word for the
parameter. If the parameter value is accepted by the Drive, the status
byte in word four will indicate that the message was successful. If the
message status indicates an error, then the PLC Controller program
must check the parameter status word to determine which parameter(s)
was not accepted by the Drive.