Bulletin 284e trip status – Rockwell Automation 284E ArmorStart EtherNet IP Communications and Control Programming Manual User Manual
Page 72
![background image](/manuals/577532/72/background.png)
72
Rockwell Automation Publication 280E-PM001A-EN-P – August 2011
Appendix A ArmorStart
®
EtherNet/IP
™
Communications & Control Programming Manual
Bulletin 284E Trip Status
The table below shows the default input (produced) assembly for Bulletin 284E.
Bytes 10 and 11 make up the word called Parameter 14 Prod Assy Word 1. The
Prod Assy Word
points to a parameter and returns the value of that parameter. In
this case, Parameter 14 Prod Assy Word 1 points to Parameter 4, which is the
Trip Status
parameter. Cross reference the Parameter 14 Prod Assy Word 1 value
to the Trip Status parameter definition to understand what faults are being
reported.
Bit
Function
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
— — — — — — — — — — — — — — —
X
Short Circuit
— — — — — — — — — — — — — —
X
—
Overload
— — — — — — — — — — — — —
X
— —
Phase Loss
— — — — — — — — — — — —
X
— — —
Reserved
— — — — — — — — — — —
X
— — — —
Reserved
— — — — — — — — — —
X
— — — — —
Control Power
— — — — — — — — —
X
— — — — — —
I/O Fault
— — — — — — — —
X
— — — — — — —
Over Temperature
— — — — — — —
X
— — — — — — — —
Phase Imbalance
— — — — — —
X
— — — — — — — — —
A3 Power Loss
— — — — —
X
— — — — — — — — — —
Reserved
— — — —
X
— — — — — — — — — — —
Reserved
— — —
X
— — — — — — — — — — — —
EEprom
— —
X
— — — — — — — — — — — — —
HW Fault
X
X
— — — — — — — — — — — — — —
Reserved
Produce Assembly – Instance 151 “Drive Status” – Bulletin 284E Starters
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved (Referenced in the Add-On-Profile as “Fault”)
1
Reserved (Referenced in the Add-On-Profile as “Fault”)
2
Reserved (Referenced in the Add-On-Profile as “Fault”)
3
Reserved (Referenced in the Add-On-Profile as “Fault”)
4
At Reference
Net Ref Status
Net Ctl Status
Ready
Running Rev
Running Fwd
Warning
Tripped
5
Contact2
Contact1
140M On
HOA
Input 4
Input 3
Input 2
Input 1
6
Output Frequency (Low) (xxx.x Hz)
7 Output
Frequency
(High) (xxx.x Hz)
8
Net Out 8
Net Out 7
Net Out 6
Net Out 5
Net Out 4
Net Out 3
Net Out 2
Net Out 1
9
Logic Enable
Net Out 15
Net Out 14
Net Out 13
Net Out 12
Net Out 11
Net Out 10
Net Out 9
10
Value of the parameter pointed to by "Parameter 13 Prod Assy Word 0" (low byte)
11
Value of the parameter pointed to by "Parameter 13 Prod Assy Word 0" (high byte)