beautypg.com

Rockwell Automation 284E ArmorStart EtherNet IP Communications and Control Programming Manual User Manual

Page 45

background image

Rockwell Automation Publication 280E-PM001A-EN-P – August 2011

45

ArmorStart

®

EtherNet/IP

Communications & Control Programming Manual Chapter 4

6.

To identify what fault occurred:
a. Double click on Controller Tags at the top of the Controller

Organizer

b. Verify that a fault occurred within the unit by looking at the

TripPresent

tag within AS_EIP_280:I. Expand AS_EIP_280:I by

clicking on the plus sign next to AS_EIP_280:I. The TripPresent bit
should be a 1.

c. To see which fault occurred, expand AS_EIP_280:I and scroll down

and expand AS_EIP_280:I.Int01DeviceOut to see the individual bits
of this word. AS_EIP_280:I.Int01DeviceOut points to parameter 4
which is Trip Status. These 16 bits correlate to the Trip Status bit
description in the

Bulletin 280E Trip Status

section on page

71

.

d. Compare the bits of AS_EIP_280:I.Int01DeviceOut to the Trip Status

definition in the

Bulletin 280E Trip Status

section on page

71

. Verify

the reported fault matches the fault that was created.

This manual is related to the following products: