beautypg.com

Rockwell Automation 284E ArmorStart EtherNet IP Communications and Control Programming Manual User Manual

Page 58

background image

58

Rockwell Automation Publication 280E-PM001A-EN-P – August 2011

Chapter 5 ArmorStart

®

EtherNet/IP

Communications & Control Programming Manual

6.

This screen will pop up indicating that the parameters have been reset to
their default values. Click OK to continue.

7.

Scroll down so you can view parameters 24 and 131 through 140. Change
the following parameters as shown in the figure below.
a. Parameter 24 allows the user to enable or disable various protection

faults. Click on the value for parameter 24 and, using the scroll bar,
scroll down and check the box next to A3 Power Loss to enable this
fault. Choosing this causes the unit to fault if the unswitched A3
terminal power drops below 12V DC. The unswitched A3 terminal
powers both the inputs and the communications.

b. Parameter 131 is where the user enters the voltage rating of the motor as

specified on the motor name plate (NP). Set parameter 131 to 220V.

c. Parameter 132 is where the user enters the motor frequency rating as

specified on the motor name plate (NP). Set parameter 132 to 30 Hz.

d. Parameter 133 sets the maximum allowable current. The unit will fault

if the value of this parameter is exceeded by 150% for 60s. Set parameter
133 to 2.0.

e. Parameter 134 sets the minimum frequency value the unit will output

continuously. Leave parameter 134 at 0 Hz.

f. Parameter 135 sets the highest frequency value the unit will output

continuously. Set parameter 135 to 65 Hz.

g. Parameter 136 sets the control scheme used to start the unit. Leave

parameter 136 at Comm Port so that the unit can be controlled via the
EtherNet network.

h. Parameter 137 sets the stop mode for the unit. Using the drop-down

box, change parameter 137 to Coast.

i. Parameter 138 sets the speed reference for the unit. Using the drop-

down box, change parameter 138 to Preset Freq. Reference parameters
170…177 to view the preset frequency values.

j. Parameter 139 sets the rate of acceleration for all speed increases by

setting the acceleration time in seconds. Set parameter 139 to 15
seconds

.