Using I/O Messaging

5-7

20-COMM-K CANopen Adapter User Manual

Publication 20COMM-UM012B-EN-P

(Parameter 82 / Parameter 55) * 32767 = Scaling

Using parameter 82 and 55 default values, speed Reference scaling is:

(60 Hz / 130 Hz) * 32767 = 15123

Therefore, 0…15123 = 0…60.0 Hz.

If parameter 82 - [Maximum Speed] is changed to 90 Hz, then:

(90 Hz / 130 Hz) * 32767 = 22685

Therefore, 0…22685 = 0…90.0 Hz.

A graphic representation of this Reference scaling is shown below:

For PowerFlex 70 EC drives (firmware v2.xxx or higher) or PowerFlex 700
VC drives (firmware v3.xxx or higher), parameter 298 - [DPI Ref Select]
was added to simplify scaling for the speed Reference. When parameter 298
- [DPI Ref Select] is set to its default “0” (Max Freq), the speed Reference
scaling is as shown above. However, when parameter 298 - [DPI Ref Select]
is set to “1” (Max Speed), the speed Reference scaling is equal to parameter
82 - [Max Speed]:

Parameter 82 = Scaling

Therefore, 0…32767 = 0…60.0 Hz.

If parameter 82 - [Maximum Speed] is changed to 90 Hz, then:

90 Hz = 32767

Speed Feedback uses the same scaling as the speed Reference.

For Reference/Feedback details about other DPI drives, refer to their
respective User Manuals.

0

0 Hz

P

ar

. 55 - [Maxim

um F

req]

Par. 82 - [Maxim

um Speed]

130 Hz

90 Hz
60 Hz

32767

22685

15123

Scaling = (Parameter 82 / Parameter 55) * 32767

TIP: For PowerFlex 700 VC drives (firmware v3.xxx or higher), Parameter
299 - [DPI Fdbk Select] enables you to select the feedback data coming
from the drive over DPI. The default is “Speed Fdbk” in Hz or RPM
determined by Parameter 079 - [Speed Units]. The data selection for
Parameter 299 is also displayed on the 1st line of the HIM and on
DriveExplorer and DriveExecutive screens in the drive status area of the
screen.