Function library, Function blocks – Lenze EVS9332xP User Manual
Page 226

Function library
Function blocks
3.5.39
Freely assignable input variables (FEVAN)
3−198
l
EDSVS9332P−EXT DE 2.0
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
FEVAN6−IN
a
C1548
dec
C1546
1
Input value
FEVAN6−LOAD
d
C1549/1
bin
C1547/1
2
A LOW−HIGH edge transmits the converted signal to the
target code.
FEVAN6−BUSY−IN
d
C1549/2
bin
C1547/2
2
HIGH = transmitting
FEVAN6−FAIL−IN
d
C1549/3
bin
C1547/3
2
High = transmission failed
FEVAN6−BUSY
d
−
−
−
−
HIGH = transmitting
FEVAN6−FAIL
d
−
−
−
−
HIGH = transmission failed
A LOW−HIGH edge at FEFAN6−LOAD sets FEFAN6−FAIL
= LOW.
−
−
C1540
−
−
−
Display of the converted signal
Function
l
Conversion of the read data via:
– Numerator, denominator.
– Offset.
l
Selection of a target code for the read data.
Codes for the conversion of the data read and for the selection of the target code
Selection of the target code
Function block
Numerator
Denominator Offset
Code
Subcode
Examples
FEVAN1
C1093
C1094
C1095
C1091
C1092
FEVAN2
C1503
C1504
C1505
C1501
C1502
FEVAN3
C1513
C1514
C1515
C1511
C1512
FEVAN4
C1523
C1524
C1525
C1521
C1522
FEVAN5
C1533
C1534
C1535
C1531
C1532
FEVAN6
C1543
C1544
C1545
C1541
C1542
Data transmission
FEVANx-FAIL
FEVANx-BUSY
FEVANx-LOAD
Correct transmission
Wrong transmission
Fig. 3−151
Signal flow
Transmission errors may occur if
l
no target code is available,
l
no target subcode is available,
l
the data transmitted are out of the target code limits,
l
the target code is inhibited since it may only be written if the controller is inhibited. Inhibit the
controller (see code table).