4 error codes, Parameter data transfer – Lenze EMF2178IB User Manual
Page 76

Parameter data transfer
Error codes
l
76
EDSMF2178IB EN 3.0
10.4
Error codes
Error code
[hex]
Description
0x05030000
Toggle bit not changed
0x05040000
SDO protocol expired
0x05040001
Invalid or unknown client/server command specifier
0x05040002
Invalid block size (only block mode)
0x05040003
Invalid processing number (only block mode)
0x05040004
CRC error (only block mode)
0x05040005
Not enough memory
0x06010000
Object access not supported
0x06010001
Try to read writable object
0x06010002
Try to write readable object
0x06020000
Object not listed in object directory
0x06040041
Object not mapped to PDO
0x06040042
Number and length of objects to be transferred longer than PDO.
0x06040043
General parameter incompatibility
0x06040047
General internal controller incompatibility
0x06060000
Access denied because of hardware error
0x06070010
Inappropriate data type, service parameter length
0x06070012
Inappropriate data type, service parameter length exceeded
0x06070013
Inappropriate data type, service parameters not long enough
0x06090011
Subindex does not exist
0x06090030
Parameter value range exceeded
0x06090031
Parameter values too high
0x06090032
Parameter values too low
0x06090036
Maximum value falls below minimum value
0x08000000
General error
0x08000020
Data cannot be transferred or stored for the application.
0x08000021
Because of local control, data cannot be transferred or stored for the application.
0x08000022
Because of current controller status, data cannot be transferred or stored for the
application.
0x08000023
Dynamic generation of object directory not successful or no object directory available
(e.g. object directory generated from file, generation not possible because of a file
error).