15 i-1017: producer heartbeat time, 16 i-1018: module device description, 17 i-1029: error behaviour – Lenze EMF2178IB User Manual
Page 106: 15 i−1017: producer heartbeat time, 16 i−1018: module device description, 17 i−1029: error behaviour, Implemented canopen objects

Implemented CANopen objects
Overview
I−1017: Producer heartbeat time
l
106
EDSMF2178IB EN 3.0
13.2.15
I−1017: Producer heartbeat time
Index (hex)
0x1017
Name
Producer heartbeat time
Subindex
Default
setting
Value range
Access
Data type
0
0
0
...
65535 rw
U32
The heartbeat telegram will be sent automatically if a value > "0" is entered in I−1017. The
cycle time corresponds to the entered value in milliseconds.
"Node guarding" is deactivated when the "heartbeat time" is active.
13.2.16
I−1018: Module device description
Entry of vendor ID
Index (hex)
0x1018
Name
Module device description
Subindex
Default
setting
Value range
Access
Data type
0
Module device description −
Module−specific
ro
Identity
...
4
Subindices
Subindex
Meaning
0
Highest subindex
1
Vendor ID = ID assigned to Lenze by the organisation "CIA"
2
Product code
3
Revision number
4
Serial number
13.2.17
I−1029: Error behaviour
Index (hex)
0x1029
Name
Error characteristics
Subindex
Default
setting
Value range
Access
Data type
0
No. of error classes
−
0
...
255 ro
U8
1
Communication error
−
0
...
2 rw
U8
Subindex 1
Value of
subindex 1
Meaning
0
Status change to "Pre−operational"
1
No status change
2
Status change to "Stopped"
Here, the response to communication errors (node guarding, heartbeat) can be set under
subindex 1.