13 parameter reference, C01120 | sync signal source, C01501 | reaction on communication error with mci – Lenze E84AYCET EtherCAT MCI module User Manual
Page 96: Parameter reference, C01120, C01501
13
Parameter reference
13.1
Communication-relevant parameters of the standard device
96
Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13
Parameter reference
This chapter supplements the parameter list and the table of attributes in the software manual and
in the »Engineer« online help for the Inverter Drive 8400 by the parameters of the E84AYCET
communication module (EtherCAT).
13.1
Communication-relevant parameters of the standard device
This chapter lists the communication-relevant parameters of the Inverter Drive 8400 in numerically
ascending order.
C01120
C01501
Software manual/online help for the Inverter Drive 8400
Here you will find general information about parameters.
Parameter | Name:
C01120 | Sync signal source
Data type: UNSIGNED_8
Index: 23455
d
= 5B9F
h
Selection of the source for DC synchronisation signals.
• Select "4: MCI" for the communication module.
• In general, only one source can synchronise the drive.
Synchronisation with "Distributed Clocks" (DC) ( 37)
Selection list
(Lenze setting printed in bold)
Info
0 Off
Synchronisation off
1 CAN on board
Synchronisation via the system bus "CAN on board"
4 MCI
Synchronisation via MCI (communication module)
;
Read access ; Write access CINH PLC-STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01501 | Reaction on communication error with MCI
Data type: UNSIGNED_8
Index: 23074
d
= 5A22
h
Configuration of monitoring functions for the communication module
Selection list
0 No response
1 Error
2 Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
Subcodes
Lenze setting
Info
C01501/1
0: No response
Reaction on MCI communication failure
• Response to a communication error (module in slot)
C01501/2
0: No response
Reaction on MCI module invalid
• Response to an incompatible communication module
or module not in slot
;
Read access ; Write access CINH PLC-STOP No transfer COM MOT
Scaling factor: 1