Operational status quit [0x01bc8131, Sync telegram failure [0x01bc8700, Error m – Lenze E84AYCET EtherCAT MCI module User Manual

Page 95: Operational status quit, 0x01bc8131] ( 95), 0x01bc8131, 0x01bc8700, 12 error messages

background image

Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17

95

12

Error messages

12.2

Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Operational status quit [0x01bc8131]

Sync telegram failure [0x01bc8700]

Response (Lenze setting printed in bold)

Setting:

C13880/1

(; Adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

The EtherCAT data exchange was stopped in the

"Operational" state.

See also chapter "

Interruption of EtherCAT

communication

"

( 82)

.

• Check cables and terminals.

• The master has to reset the node to the "Operational"

status. (If required, check a pending emergency

message first).

Response (Lenze setting printed in bold)

Setting:

C13880/2

(; Adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked … Warning ; Information

Cause

Remedy

• The cycle time settings are faulty.

• The task time setting of a linked PLC program is faulty.

• EtherCAT master / DC master settings are incorrect.

• The sync source setting is faulty.

• Check the cycle times.

• Check the task time of a linked PLC program.

• Check the EtherCAT master / DC master settings.

• Check the settings in

C01120

of the standard device

(selection of the sync source).