beautypg.com

C13887 | suppress emergency message in case of, C13899 | station alias, C13900 | firmware: product type – Lenze E84AYCET EtherCAT MCI module User Manual

Page 101: C13901 | firmware compilation date, N to code, C13899, C13887, C13900, C13901, 13 parameter reference

background image

Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17

101

13

Parameter reference

13.2

Parameters of the communication module

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13887

C13899

C13900

C13901

Parameter | Name:

C13887 | Suppress emergency message in case of

Data type: BITFIELD_8

Index: 10688

d

= 29C0

h

This code serves to prevent the emergency messages from being transmitted to the EtherCAT master. Here, errors

of a certain type can be suppressed deliberately. Furthermore, all errors are entered in the logbook.

A change will only be effective if no error number with the error type selected here is available in the standard device

code C00165.
Value is bit-coded:

Info

Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Information
Bit 6 Reserved
Bit 7 Reserved

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13899 | Station alias

Data type: UNSIGNED_16

Index: 10676

d

= 29B4

h

This code serves to set a station alias address.

In order to use a station alias address, you must select a value > '0'.

• The station alias address must only be set if the node is part of a "hot connect" group.

• The station alias address must be unambiguous and may only be assigned once within the EtherCAT network.

• Use the same station alias address in the EtherCAT master and in the slave.

Address allocation ( 36)

Setting range

(min. value | unit | max. value)

Lenze setting

0

32767 0

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT

Parameter | Name:

C13900 | Firmware: Product type

Data type: VISIBLE_STRING

Index: 10675

d

= 29B3

h

The code contains a string with a length of 8 bytes.

The following identification code is output:

• "E84AFCET" (up to V01.05)

• "E84AFYET" (from V02.00)

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13901 | Firmware compilation date

Data type: VISIBLE_STRING

Index: 10674

d

= 29B2

h

The code contains a string with a length of 20 bytes. The creation date ("MM DD YYYY") and the time ("hh:mm:ss")

of the software are output here.

Example: "Mar 21 2005 12:31:21"

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT