beautypg.com

5installation – Lenze E84AYCET EtherCAT MCI module User Manual

Page 32

background image

5

Installation

5.2

Electrical installation

32

Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Assignment of the X245 plug connector

Terminal data

Designation

Description

+

U = 24 V DC (20.4 V - 0 % ... 28.8 V + 0 %)

I = 140 mA

-

Reference potential for the external voltage supply

Area

Values

Electrical connection

2-pole plug connector with spring connection

Possible connections

Fixed:

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

Flexible:

Without wire end ferrule

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

With wire end ferrule, without plastic sleeve

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

With wire end ferrule, with plastic sleeve

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

Stripping length

10 mm