Data transfer

7.3

EtherCAT state machine

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.3

EtherCAT state machine

Before communication is possible via EtherCAT, the fieldbus passes through the EtherCAT state

machine during start-up. The following illustration depicts the possible state changes from the

point of view of an EtherCAT slave:

[7-1]

EtherCAT state machine

The current status of the EtherCAT state machine is shown in

C13861

and indicated via the BS LED.

Possible errors at the state transitions are shown in

C13879

. Additionally, an error message is

entered in the "AL status code" EtherCAT register"

( 58)

.

E94AYCET009

Operational

Pre-Operational

Init

Safe-Operational

State

Description

Init

• Initialisation phase

• No SDO/PDO communication with the slaves

• Device detection possible by means of a fieldbus scan

Pre-operational

• The fieldbus is active.

• SDO communication (mailbox communication) is possible.

• No PDO communication

Safe-operational

• SDO communication (mailbox communication) is possible.

• PDO communication:

• The input data in the process image are updated.

• The output data from the process image are not transferred to the slaves.

Operational

Normal operation:

• SDO communication

• PDO communication

• Fieldbus synchronisation successful (if used)

Note!

• A fieldbus scan can be carried out during any EtherCAT status.
• SDO communication via the EtherCAT bus is only possible if at least the "Pre-

Operational" state has been reached.

• Only in the transitional phases between states can bus nodes be in different states.