6commissioning – Lenze E84AYCET EtherCAT MCI module User Manual
Page 39
Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17
39
6
Commissioning
6.4
Synchronisation with "Distributed Clocks" (DC)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4.3
Response of the Lenze EtherCAT nodes during start-up
Code
indicates whether the DC synchronisation for the communication module has been
activated.
If the DC synchronisation is used, the communication module only changes to the "Operational"
state when the standard device has adapted its phase position to the DC signal. This process may
take several seconds.
The state of the standard device synchronicity is displayed under code
Note!
• If the communication module does not change to the "Operational" state, there might
be an error in the configuration or in the EtherCAT wiring.
• The communication module compares the cycle time defined by the EtherCAT master
to the internal processing time (1 ms) of the standard device. The synchronisation
cycle time in the master must be identical with or an integer multiple of 1 ms.
• Furthermore it is checked whether the sync source selection in standard device code
is correct.
• Further information can be found in the status information or emergency messages
of the master.