2 reading and writing parameters, Reading and writing parameters, 9parameter data transfer – Lenze E84AYCET EtherCAT MCI module User Manual

Page 69

background image

Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17

69

9

Parameter data transfer

9.2

Reading and writing parameters

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2

Reading and writing parameters

Parameters ...

• for instance are set for one-time system settings or if materials are changed within a machine;
• are transmitted with a low priority.

In the case of Lenze inverters, the parameters to be changed are contained in codes.

Indexing of the Lenze codes
If they are accessed via a communication module, the codes of the inverter are addressed by the

index.
The index of Lenze code numbers within the manufacturer-specific area of the object directory is

between 8192 (0x2000) and 24575 (0x5FFF).

Structure of a mailbox datagram
Mailbox data are transmitted in a datagramm within an EtherCAT frame. The data area of the

mailbox datagram has the following structure:

Conversion formula
Index [dec]

Index [hex]

24575 - Lenze code

0x5FFF

- Lenze code

hex

Example of C00002 (device commands)
Index [dec]

Index [hex]

24575 - 2 = 24573

0x5FFF - 2 = 0x5FFD

Mailbox

Header

CoE

Header

SDO control

byte

Index

Subindex

Data

Data

6 bytes

2 bytes

1 byte

2 bytes

1 byte

4 bytes

1 ... n bytes