Internal error [0x01bc6011, Internal error [0x01bc6100, Internal error [0x01bc6101 – Lenze E84AYCET EtherCAT MCI module User Manual

Page 94: Invalid parameter set [0x01bc641f, Error: lenze setting loaded [0x01bc6420, Invalid module configuration [0x01bc6430, Invalid module configuration, 0x01bc6430] ( 94), 0x01bc6011, 0x01bc6100

background image

12

Error messages

12.2

Possible causes and remedies

94

Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Internal error [0x01bc6011]

Internal error [0x01bc6100]

Internal error [0x01bc6101]

Invalid parameter set [0x01bc641f]

Error: Lenze setting loaded [0x01bc6420]

Invalid module configuration [0x01bc6430]

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Communication module is defective.

Send communication module with error description to

Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Communication module is defective.

Send communication module with error description to

Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Communication module is defective.

Send communication module with error description to

Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

No active parameter set could be loaded.

Repeat download of the application (including module).

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Access via standard device to parameter set within the

memory module was not successful.

Repeat download of the application (including module).

Response (Lenze setting printed in bold)

Setting: not possible

:

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

• Faulty module configuration.

• Incorrect sync settings.

Check and correct module configuration/sync settings.