4 configuration parameters – JUMO 706560 LOGOSCREEN es Operating Manual User Manual

Page 82

background image

4 Configuration parameters

82

Differential
(hysteresis)
(analog channels,
group 1 — 6)

Configuration
➔ Group config.

➔ Group 1 — 6

➔ Analog channels

➔ Analog channel

1 — 6
➔ Differential

-99999 to 0 to +99999

(1) = Low limit
(2) = High limit
(3) = Differential

Text low alarm
(analog channels,
group 1 — 6)

Configuration
➔ Group config.

➔ Group 1 — 6

➔ Analog channels

➔ Analog channel

1 — 6
➔ Text

low alarm

Standard text,
Text 1 — 146,
No text

v Chapter 3.5 “Event list /

AT”

v Configuration ➔ Texts,

page 91

Text high alarm
(analog channels,
group 1 — 6)

Configuration
➔ Group config.

➔ Group 1 — 6

➔ Analog channels

➔ Analog channel

1 — 6
➔ Text

high alarm

Standard text,
Text 1 — 146,
No text

v Chapter 3.5 “Event list /

AT”

v Configuration ➔ Texts,

page 91

Alarm delay
(analog channels,
group 1 — 6)

Configuration
➔ Group config.

➔ Group 1 — 6

➔ Analog channels

➔ Analog channel

1 — 6
➔ Alarm

delay

0 — 32767s

Alarm delay is activated at
a value of <> 0.
When activated, an alarm
will only be generated
when it has been present
for at least as long as it
takes for the set time to
elapse.

Parameter

Value/selection

Description

(1)

(2)

(3)

(3)

Alarm ON

Alarm OFF