2 Instrument description

2.6 Integrator

In addition to minimum, maximum and average value of an (analog) channel in
a group, the reports can include an integrator.

Activating the
integrator

An integrator time base has to be specified at the configuration level under
Configuration

Î

Analog inputs

Î

Analog input 1 — 12

Î

Additional

parameters, or Configuration

Î

Analog inputs

Î

External input 1 — 36

Î

Additional parameters. If no time base is given (Off), the indication of the
integrator in the reports is suppressed.

The integrator can be used to determine a total flow volume or a liquid level,
for instance, and to present it in the diagram.

Example

A sensor at analog input 1 provides a signal that is proportional to the flow rate
(m

3

/h). The volume (m

3

) which has passed through is to be measured using

the integrator.

The following settings are required:

Parameter

Value/selection

Description

Configuration
➔ Analog inputs

➔ Analog input 1

➔ Additional

parameters
➔ Unit

m

3

/h

Sensor signal proportional
to the flow rate in m

3

/h

Configuration
➔ Analog inputs

➔ Analog input 1

➔ Additional

parameters
➔ Integr.

time base

Hour

The flow is measured in
m

3

/hour (h).

Configuration
➔ Analog inputs

➔ Analog input 1

➔ Additional

parameters
➔ Integr. unit

m

3

In the reports, the volume
which has passed through
is indicated in m

3

. The

maximum integrator value
is 99999.