6 integrator, Integrator, 2 instrument description – JUMO 706560 LOGOSCREEN es Operating Manual User Manual
Page 21

21
2 Instrument description
2.6 Integrator
In addition to minimum, maximum and average value of an (analog) channel in
a group, the reports can include an integrator.
Activating the
integrator
An integrator time base has to be specified at the configuration level under
Configuration
Î
Analog inputs
Î
Analog input 1 — 12
Î
Additional
parameters, or Configuration
Î
Analog inputs
Î
External input 1 — 36
Î
Additional parameters. If no time base is given (Off), the indication of the
integrator in the reports is suppressed.
The integrator can be used to determine a total flow volume or a liquid level,
for instance, and to present it in the diagram.
Example
A sensor at analog input 1 provides a signal that is proportional to the flow rate
(m
3
/h). The volume (m
3
) which has passed through is to be measured using
the integrator.
The following settings are required:
Parameter
Value/selection
Description
Configuration
➔ Analog inputs
➔ Analog input 1
➔ Additional
parameters
➔ Unit
m
3
/h
Sensor signal proportional
to the flow rate in m
3
/h
Configuration
➔ Analog inputs
➔ Analog input 1
➔ Additional
parameters
➔ Integr.
time base
Hour
The flow is measured in
m
3
/hour (h).
Configuration
➔ Analog inputs
➔ Analog input 1
➔ Additional
parameters
➔ Integr. unit
m
3
In the reports, the volume
which has passed through
is indicated in m
3
. The
maximum integrator value
is 99999.